0.4kv低压接地棒的额定电压为400V,耐压实验45KV,1分钟没有问题。

铜线均按照国家标准制作。对地电阻如下:接线鼻之间测量直流电阻,对于25mm2,35mm2,50mm2,70mm2,95mm2,120mm2的各种截面,平均每米的电阻值应分别小于0.79mΩ,0.56mΩ,0.40mΩ,0.28mΩ,0.21mΩ,0.16mΩ。操作棒的工频耐压试验。